BELZONA SEALS OIL LEAK AND PROTECTS THE ENVIRONMENT

KHIA ID: 1512
Industry: Power (POWR)
Application: VPF-Valves, Pipes and Fittings (VPF)
Substrate: Steel
Customer Location: Electrical Substation, UK
Application Date: 2007
Products:

Belzona® 1161 (Super UW Metal)


Problem: Transformer oil leaking from the top of the transformer onto the ground was heading towards a drain in the road, posing a serious environmental problem.
Photograph Descriptions
  1. Leaking transformer
  2. Surface preparation using MBX Bristle Blaster
  3. Surface preparation completed and live leak sealed with Belzona® 1291
  4. Repair completed with application of Belzona® 1161
Application Situation
Access hatch on oil filled transformer.
Application Method
Application was carried out in accordance with Belzona Know-How System Leaflet VPF-11a. Surface was cleaned the prepared with MBX Bristle Blaster. Belzona® 1291 was used to seal the visible leaks before the application of Belzona® 1161 and Belzona® 9311 (Reinforcing Sheet).
Belzona Facts
The company was previously dealing with leaks by constant cleaning. Due to the lack of containment a proper repair was crucial. The substation provides electricity to a large area of Glasgow and could not be turned off, meaning the repair had to be carried out live. The surface tolerant capabilities of Belzona® 1161 were ideal for this repair.