Holiday Detection in Applied Coatings

 

1.    Inspection of coatings using spark testing

 

This is a high voltage technique that can be used to detect pinholes, bubbles, inclusions and thin areas in insulating coatings applied to a conductive substrate.

 

A detector generates a high DC voltage, which is supplied to a suitable probe, commonly, a long wired brush. As the probe is passed over the coated surface, a spark and audible and/or visual alarms in the detector indicate a flaw. The voltage is adjusted to suit the coating thickness.

 

The ability of the spark tester, when correctly adjusted, to detect low thickness in an applied coating makes this the preferred method of holiday detection. The metal content in Belzona 1321, Belzona 1391 & Belzona 1392 precludes the use of high voltage spark testers for carrying out final inspection for pinholes and misses.

 

Inspection using HV spark testing involves making ONE pass over the coating at 30 cm/s (1ft/sec). Multiple passes can “charge” the coating like a capacitor and cause false alarm. (See also NACE SP0188).

 

1.1    Coatings that can be inspected using a spark tester include:-

 

Belzona 1341, Belzona 1521, Belzona 2121, Belzona 2131, Belzona 2141, Belzona 4311, Belzona 4341, Belzona 5811, Belzona 5851, Belzona 5891, Belzona 1391S, Belzona 1391T, Belzona 5811DW2 and Belzona 1591.

 

1.2    False Readings

 

Some of these materials when cured in a cool or humid environment can form a surface bloom, a greasy film on the surface, and this can lead to problems during the inspection procedure. When using a high voltage spark tester it is important to remove any bloom that may have formed on the surface of the coating which will lead to surface tracking.

 

If tracking occurs, a circuit will be formed across the coating surface NOT through the coating to the substrate and a drop in resistance will occur triggering a "false alarm". Tracking, caused by a surface bloom or surface condensation, should be suspected whenever an abnormal number of defects are being signalled in what appears to be a defect free coating.

 

This surface tracking can be avoided by thoroughly washing the surface of the coating using a warm detergent solution, then thoroughly drying the surface.

 

Similarly high humidity or condensation on the coating surface can cause surface tracking of the electric current generated by the equipment triggering a "false reading". These problems are particularly to be expected when working in the confines of a tank or vessel.

 

In high humidity conditions, it may be necessary to raise the surface temperature 3 – 5°C above the dew point to avoid condensation. In addition, it is advisable to maintain adequate ventilation to prevent any increase in the relative humidity within vessels. Similar problems can also be experienced when using wet sponge testers.

 

A bloom or high surface moisture liable to create false readings can be observed in several ways depending on the Instrument used. Those with a light diode in the handle will show a glow when surface tracking is occurring. Similarly a drop in voltage when the probe is moved over the surface indicates surface tracking. Instruments with the ability to display the current also see a significant rise over areas of the coating where no defects are present but have surface contamination capable of causing tracking and leakage of the applied current to earth.

 

High voltage holiday detectors with adjustable sensitivity can be adjusted to overcome some or all of the problems of "false readings". With the instrument set at the required test voltage, adjust the sensitivity such that no signal is triggered when the probe is moved over an area known to be defect free. The instrument should then still signal a defect when the probe touches the earth lead. On a heavily bloomed surface a drop in test voltage may be seen and it is acceptable to increase the test voltage to compensate for this. An excessive voltage should, however, be avoided.

 

With careful control, adjustable sensitivity spark testers may be successfully used on heavily bloomed surfaces without the need to remove the bloom. Care must, however, be taken to avoid build up of the bloom on the probe itself as this may cause discharges and false alarms. Furthermore, continual use on a conductive surface may lead to rapid drain on the spark tester's battery. Units with sufficient battery capacity should be used or facilities made available for recharging.

 

2.    Inspection of applied coatings using the Wet Sponge Tester

 

2.1    Why Wet Sponge Test?

 

As you are probably aware, the metal content in Belzona® 1321 & Belzona® 1391 precludes the use of high voltage spark testers for carrying out final inspection for pinholes and misses. This leaves visual inspection or low voltage sponge testing as the only option.

 

2.2    The principle of the Wet Sponge Test

 

The principle of the wet sponge tester is that a sponge, soaked with a wetting agent, is supplied with a low voltage, typically 90 volts. When the sponge is moved over a pinhole, liquid flows to the substrate and completes the electrical circuit. The resulting current flow generates an audible alarm in the detector.

 

2.3    False readings

When using a wet sponge tester it is important to remove any bloom that may have formed on the surface which will lead to surface tracking. If tracking occurs, a circuit will be formed across the coating surface NOT through the coating to the substrate and a drop in resistance will occur triggering a "false alarm". Tracking, caused by a surface bloom or surface condensation, should be suspected whenever an abnormal number of defects are being signalled in what appears to be a defect free coating.

 

Remove all surface bloom from the coating, using a warm detergent solution. Thoroughly dry the surface and then carefully inspect for any signs of a residual greasy film. Repeat this procedure as necessary until the surface is totally clean.

 

In high humidity conditions it may be necessary to raise the surface temperature 3-5°C above the ambient air temperature to avoid condensation.

 

Make sure that the sponge on the wet sponge tester is uncontaminated, or alternatively fit a new sponge. (Note: Residual amine bloom on the sponge has been seen to re-contaminate the surface and cause tracking.)

 

Moisten the sponge using tap water, mixed with 1 part Surfactant (typically washing up liquid) to 128 parts tap water, squeezing out any excess water.

 

The risk of tracking will be increased if a film of water is allowed to form over a large area or there is running water. To avoid this, there must only be sufficient water in the sponge to wet the immediate contact areas.

 

Conduct the test over individual areas of approximately 0.5 sq.m., drying each area after testing before going on to the next. Two passes should be made at a maximum speed of 30 cm/s (1 ft/s). Any area deemed to require repair should be marked with a marker that is easily removed. The area around the defect should then be dried and the test continued in an adjacent area. All discontinuities must be repaired and those areas re-checked.

 

Note. Although Amine bloom film is most commonly formed during the cure of the material it can, under certain circumstances, also reform after initially being removed. Therefore, following remedial work it will be necessary to wash the repaired area and the area immediately surrounding the repair before carrying out the re-test.

 

2.4    Coating thickness limitations

 

There has been some confusion as to the role of low voltage sponge testers in the inspection of Belzona® coatings. Published data from Manufacturers of these instruments limits their use to coatings below 500 microns thick. This is in line with various international standards covering their use. Manufacturers have confirmed our own tests which have shown that carefully used a sponge tester will pick up a miss in the coating above 500 microns, subject to the need to wash the coating as above.

 

2.5    Inspection during coating

 

Care during application and visual inspection, is far more important than a wet sponge test. The latter will only show a complete miss through to the substrate. Any thin areas, even where the covering may be no more than 50-100 microns, will not be found or indicated by the sponge tester. Inspection of the thick, single coat applications, particularly during application is critical to ensure a continuous defect free coating is achieved.

 

The demand for post application inspection, for new coatings in our range does feature a requirement for them to be spark testable if possible. However, the ultimate performance of the coating is paramount and the metal fillers used in Belzona® 1391 and Belzona® 1321 are critical to the erosion resistance and performance in service of these coatings. For the foreseeable future, therefore, we must continue to inspect these materials visually, assisted by the sponge test, albeit not ideal, as the only inspection tool available.

 

2.6    Equipment Suppliers

 

England
Elcometer Limited
Edge Lane
Manchester
M43 6BU
Tel: +44 (0)161 3716000
Fax: +44 (0)161 3716010

 

Buckleys (UVRAL) Ltd
Beta Works
Range Road
Hythe
Kent
CT21 6HG
Tel: (01303) 260127
Fax: (01303) 262115

 

Paint Test Equipment
3/4 The Courtyard
Greenfield Farm Estate
Congleton
Cheshire
CW 12 4TR
Tel: (01260) 275614
Fax: (01260) 299231

 

USA
Elcometer Inc
1893 Rochester Industrial Drive
Rochester Hills
Michigan 48309
Tel: +1 248 650 0500

Germany
Elcometer Instruments GmbH
Ulmer Strasse 68

D-73431 Aalen

Tel: +49 (0)7361 528060

 

Asia & Far East
Elcometer (Asia) Pte Ltd
896 Dunearn Road
Sime Darby Centre #03-09
Singapore 589472
Tel: +65 6462 2822

Back to Inspection

 

Modified July/13/2011

 
Copyright © 2011. All rights reserved. No part of this work covered by the copyrights hereon may be reproduced or used in any form or by any means – graphic, electronic or mechanical including photocopying, recording, taping or information storage and retrieval systems – without written permission of the publisher.
Belzona® is a registered trademark