| Belzona Elastomers Seal Sf6 Gas Leaks At Hydroelectric Facility | | | | Industry:Power (POWR) | | | | Application:Gaskets, Seals and Shims (GSS) | | | | Customer Location:Hydroelectric Facility, BC | | | | Application Date:1993 | | | | Application Situation:Leaking joints Gas Insulated Switchgear (GIS) | | | | Problem:The constant leakage of Sulphur Hexafluride gas (SF6) was considered to be a major environmental problem being 25,000 times as effective a "greenhouse gas" as CO2. System is pressurized to 45 psi. | | | | Products:Belzona® 2211 (MP Hi-Build Elastomer)
Belzona® 2221 (MP Fluid Elastomer)
Belzona® 1321 (Ceramic S Metal) | | | | Substrate:Various metal substrates | | | | Application Method:Application was carried out in accordance with Belzona Know-How System Leaflet GSS-4. Pinholes in welds were coated with Belzona® 1321. Flanged joints were sealed with Elastomer using a combination of brush application and injection. | | | | Belzona Facts:The Belzona materials applied in 1993 have proven completely effective with joints and welds sealed with Belzona materials remaining sealed for well over a decade now. SF6 consumption has dropped from over 50 bottles per year, to a mere two or three bottles—a saving in excess of $1 million over the decade. Most importantly losses of SF6 into the atmosphere have been minimized, drastically reducing the environmental impact. | | | | Photographs Description
- Belzona® 2211 MP Hi-Build in the process of being injected into the gap between the two flanges
- Another variation of a similar application
- Another flange sealed
| |
| |