BELZONA MAINTAINS CORRODED SPRINKLER TANK BY PLATE BONDING

KHIA ID: 4898
Industry: General Industry (GIND)
Application: TCC-Tanks and Chemical Containment Areas (TCC)
Substrate: Steel
Customer Location: Industrial Foam Manufacturer, Northamptonshire UK
Application Date: December 2013
Products:

Belzona 1161 (Super UW Metal)

Belzona 5831 (ST Barrier)


Problem: Over several years the tank had become badly corroded around approx. 50% of the circumference at the water line causing it to split open in some areas allowing water to flow out.
Photograph Descriptions

1. Large sprinkler tank with corrosion at water line 2. Surface being prepared with MBX Bristle Blaster 3. 400mm long x 300mm high steel plates being installed using Belzona 1161 4. Installation complete around tank circumference and coated with Belzona 5831

Application Situation
6m diameter x 6m high circular steel tank supplying water  for the fire sprinkler system in a large foam manufacturing plant
Application Method
Application was carried out in accordance with Belzona Know How System Leaflets TCC-1 and TCC-5. Doubler plates were bonded in place with Belzona 1161 before applying Belzona 5831 for overall corrosion protection.
Belzona Facts
For fire safety reasons the tank needed to be constantly on line, 24 hours a day, 7 days a week so replacing it with a new tank was not an option due to time and budget. Belzona repair completed with tank on-line.