Problem: The main flange was discharging high volumes of oil through the failed gasket system, together with loss through the top and bottom bolt heads. Continual tightening of the bolts was no longer proving effective on this aged transformer. The Client sought a comprehensive solution to seal the main flange and bolt heads.
Photograph Descriptions

Transformer prior to application Close up substrate preparation Main flange sealed and bolt head encapsulation Repair areas completed following Belzona 5831 coating

Application Situation
Supply Transformer ST6 located at electricity substation within steel manufacturing plant.
Application Method
Application was carried out in accordance with Belzona System Leaflet VPF-11. Due to a strict outage period and to enhance full success, the Client dropped the oil level beneath the flange level and created the correct working habitat and heat source to reduce product cure time. Substrate was prepared by MBX Bristle Blaster. Residual leaks were sealed with Belzona 1291 & 1221. Flange joint was sealed by applying Belzona 1161 & Belzona 9341 (Reinforcement Tape).  The bolt and nut heads were fully encpasulated using a disposable former containing Belzona 1161. Once cured the formers were removed and the prescribed repair areas coated with Belzona 5831.
Belzona Facts
The leak sealing application was successful following recharge of oil and when the transformer was placed back in service. The flange and bolt heads have shown no further  signs of leaking. This has resulted in significant cost saving and eliminated risk to the local environment. Belzona provided a full turnkey solution to the Client.