Belzona Stops Cooling Tower Leaks

KHIA ID: 527
Industry: Power (POWR)
Application: FPA-Floor Problem Areas (FPA)
Substrate: Concrete
Customer Location: Independent Power Plant in South Texas, USA
Application Date: March 2005
Products:

Belzona 2211 (MP Hi-Build Elastomer)

Belzona 2221 (MP Fluid Elastomer)

Belzona 2911 (Elastomer QD Conditioner)


Problem: Leaks in expansion joints were causing losses of valuable cooling water. Client needed a cost effective way to stop the leaks.
Photograph Descriptions

1. Large Cooling Tower

2. Joint blasted and backer installed

3. Belzona 2221 being poured into joint

4. Next day- finished repair. Joint holds back rainwater.

Application Situation
Plant planned a short outage to seal the water leaks. Belzona needed to be there non-stop to supervise these repairs.
Application Method
Remove old sealants. Grit blast and and insert backer. Apply 2911 and Belzona 2211 to verticals and Belzona 2221 to horizontals.
Belzona Facts
The use of Belzona elastomers was cost effective over alternativ materials. Belzona know how allowed for a faster repair than alternatives.