Belzona repairs transformer cooling fins
Industry: Power (POWR)
Application: TCC-Tanks and Chemical Containment Areas (TCC)
Substrate: Carbon steel
Customer Location: Scotland
Application Date: May 2017
Products: Belzona 1161 (Super UW-Metal),Belzona 5831 (ST-Barrier)
Problem: Transformer cooling fins had become corroded from water collecting on the fins edges & started to leak
Areas overcoated with Belzona 5831
Application Situation
Welding was not possible due to the oil in the fins. By using a cold applied system repairs could be undertaken promptly & safely
Application Method
The fins were prepared using Dremel type tools & small grinders. 'U' shaped doubler plates were then bonded using Belzona 1161 UW Metal on the most corroded fins. All areas were then overcoated using Belzona 5831 to provide corrosion protection.
Belzona Facts
Dozens of plate bonds have now been done at this site with very little disruption to operations.