BELZONA REPAIRS TRANSFORMER FLANGE OIL LEAK

KHIA ID: 1491
Industry: Buildings & Structures (BSTR)
Application: GSS-Gaskets, Seals and Shims (GSS)
Substrate: Steel
Customer Location: Arizona, USA
Application Date: July 1992
Products:

Belzona 2221 (MP Fluid Elastomer)

Belzona 1221 (Super E-Metal)


Problem: Oil leaks raised maintenance, EPA and safety concerns. Replacement of gaskets would require shut-down and dismantling of equipment.
Photograph Descriptions

1. Oil leak area of transformer

2. Seal with Belzona 1221, then pour Belzona 2221 encapsulated the flange

3. Application completed

 

Application Situation
Flanged pipe connections on transformer flange at the major power company.
Application Method
The application was carried out in accordance with a modified of Belzona Know-How System Leaflet VPF-11 and GSS-4. Leaks were firstly stopped by using Belzona 1221. Mould was constructed and a fluid grade of Belzona 2221 was poured in to encapsulate the flange.
Belzona Facts
Repairs were carried out in-situ without the need to take the transformer off-line. Savings were estimated at $150,000. The repaired flange was in continuous operation for over 4 years.