Belzona Florida Repairs water Discharge Flange
Industry: Power (POWR)
Application: VPF-Valves, Pipes and Fittings (VPF)
Substrate: Concrete
Customer Location: Fort Lauderdale, Florida
Application Date: December 2023
Products: Belzona 1111 (Super Metal), Belzona 1321 (Ceramic S-Metal)
Problem: The customer had a non-Belzona coating previously applied that failed, causing corrosion scaling on the interior edge of the flange.
Showcasing and measuring the damage caused by the corrosion.
Showcasing and measuring the damage caused by the corrosion.
Rebuilding the damage using Belzona 1111.
Application of Belzona 1321.
Application Situation
Belzona offered time savings and replacement of failed non-belzona coating.
Application Method
Removed corrosion scaling with pneumatic chipping guns and needle scalers. A high pressure grit blaster with 24 grit aluminum oxide was utilized to obtain a SSPC SP-10 level of cleanliness with a minimum surface profile of 3 mils. Keane-Tator Surface Profile Comparator grit was used to verify the surface profile. The area was then soaked with demineralized water and left to sit overnight to allow chlorides to leech out. Then it was brush blasted with 30 grit aluminum oxide back to SSPC SP-10.
Belzona Facts
Saved the company downtime and provided them with a long lasting and reliable solution.