Cooling Tower Pipe Leak Repair

KHIA ID: 9721
Industry: Oil & Gas (OILG)
Application: VPF-Valves, Pipes and Fittings (VPF)
Substrate: Carbon steel
Customer Location: Southwestern Ontario
Application Date: November 2024
Products: Belzona 1212,Belzona 1982 (SuperWrap II),Belzona SuperWrap,Accessories,Belzona 9111 (Cleaner Degreaser),Belzona 9611 (ES-Metal)

Problem: 1 inch steel pipe had corrosion and was leaking at the pipe seam and socket weld joint

X-Ray showing the socket joints and pipes

Picture showing pipe leaking.

Picture show's water leak has been stopped and application completed.

Picture show's water leak has been stopped and application completed.

Application Situation
The plant was not able to shut down the system so a solution for a live leak was requested and the end user and contractor knew Belzona would have a solution and the products for the application.
The cost was under $3,000.00 for the repair that saved the plant from shutting down the system that would have cost hundreds of thousands of dollars 2/3 weeks of down time.
Application Method
Heavy rust was removed by a tapping the pipe with a hammer and than the preparation was completed using pneumatic air hand tooling, needle gun and grinder.
Belzona Facts
Belzona was chosen for the both the end user and contractor have used many Belzona products over the years and have great success and long term results.