Backup Generator - Diesel Tank Restoration With Belzona

KHIA ID: 8498
Industry: Power (POWR)
Application: RPA-Roof Problem Areas (RPA)
Substrate: Carbon Steel
Customer Location: Florida
Application Date: 2/16/2021
Products:

Belzona 1121 (Super XL-metal)

Belzona 4911 (Magma TX- conditioner

Belzona 4131 (Magma Screed)

Belzona 5811 (Immersion grade)


Problem: Water and rust were getting into the fuel system putting equipment at risk.
Photograph Descriptions

1- Generator 

2- Section of Corrosion

3- Belzona 4911 & 4131 being applied

4- final coat of Belzona 5811

Application Situation
Severe corrosion on top of the tank leading to pinholes.
Application Method
Clean Top of the Steel Tank. Needle Gun used to remove Heavy Scale from Years of Corrosion. Surface SpongeBlasted to a SSPC-SP10 Near White Condition. If the surface preperation perforated the metal, the repair was Cold Bonded with a plate repair using Belzona 1121. One Coat of Belzona 4911 Conditioner. Install Belzona 4131 to create a slope for the water to Evacuate from the middle on both sides of the tank. Top Coat with Belzona 5811
Belzona Facts
Repair needed to be performed in a timely manner. The generator is part of local municipality energy redundancy plans and was down awaiting tank repair. Welding or replacement was not an economical option due to overall substrate conditions, fire risks, and the expense of custom fabrications.